https://www.phoenixcontact.com/gb/products/2862149
Inline terminal - IB IL AI 2-HART-PAC - 2862149
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Inline, Analog input terminal, Analog inputs: 2, 4 mA ... 20 mA, 0 mA ... 25 mA, connection method: 2-wire,
transmission speed in the local bus: 500 kbps, HART functionality, HART protocol transmission, degree of
protection: IP20, including Inline connectors and marking fields
Product Description
The terminal is designed for use within an Inline station.
It allows communication with smart field devices using the standardized communication protocols INTERBUS and HART. It provides both analog
and digital communication. The analog signal transmits the process information. The modulated digital signal enables bidirectional communication
to the sensor (with HART capabilities) at the same time.
Your advantages
Two differential signal inputs for current sensors
Connection of sensors in 2-wire technology (active and passive sensors)
Current ranges: 4 mA ... 20 mA, 0 mA ... 25 mA
Both channels preset to the 4 mA ... 20 mA measuring range and IB IL format
Transmission of the HART protocol with PCP
Measured values can be represented in three different formats
Resolution depends on the representation format and the measuring range
Measured value acquisition with 16-bit resolution
Point-to-point and multi-drop connections possible
A hand-held operator panel can be connected
A maximum of 5 HART devices can be connected per channel
Polling and burst modes
FDT/DTM support
Key Commercial Data
Packing unit
1 pc
GTIN
GTIN
4017918918835
Weight per Piece (excluding packing)
134.000 g
Custom tariff number
85389091
Country of origin
Germany
02/27/2020 Page 1 / 10
https://www.phoenixcontact.com/gb/products/2862149
Inline terminal - IB IL AI 2-HART-PAC - 2862149
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
48.8 mm
Height
135 mm
Depth
71.5 mm
Ambient conditions
Ambient temperature (operation)
-25 °C ... 55 °C
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)
10 % ... 95 % (non-condensing)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP20
General
Mounting type
DIN rail
Color
green
Net weight
134 g
Operating mode
Process data operation with 2 words, PCP with 2 words
Diagnostics messages
Failure of the internal I/O supply Yes
I/O error Error message in the process data
User error Error message in the process data
Interfaces
Designation
Inline local bus
No. of channels
2
Connection method
Inline data jumper
Transmission speed
500 kbps
Transmission physics
Copper
Inline potentials
Designation
Communications power (UL)
Supply voltage
7.5 V DC (via voltage jumper)
Current consumption
typ. 95 mA
max. 110 mA
Designation
Supply of analog modules (UANA)
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumption
typ. 50 mA
max. 150 mA
02/27/2020 Page 2 / 10
https://www.phoenixcontact.com/gb/products/2862149
Inline terminal - IB IL AI 2-HART-PAC - 2862149
Technical data
Inline potentials
Power consumption
typ. 1.9 W
Analog inputs
Description of the input
Differential inputs, current
Input name
Analog inputs
Number of inputs
2
Connection method
Inline shield connector
Connection technology
2-wire
Note regarding the connection technology
shielded
A/D conversion time
approx. 10 µs (bus-synchronous)
A/D converter resolution
16 bit
Limit frequency (3 dB)
25 Hz
Type of protection
Surge protection
Data formats
IB IL, standardized representation, PIO
Measuring principle
Successive approximation
Measured value resolution
16 bits (15 bits + sign bit)
Measured value representation
16 bit two's complement
Current input signal
4 mA ... 20 mA
0 mA ... 25 mA
Input resistance current input
250 Ω
Common mode voltage range signal - ground
40 V (between current input and functional earth ground)
Electrical isolation
Test section
7.5 V supply (bus logic), 24 V supply UANA / I/O 500 V AC 50 Hz 1 min.
7.5 V supply (bus logic), 24 V supply UANA/functional earth ground 500 V
AC 50 Hz 1 min.
I/O / functional earth ground 500 V AC 50 Hz 1 min.
Standards and Regulations
Connection in acc. with standard
CUL
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values
Drawings
02/27/2020 Page 3 / 10
https://www.phoenixcontact.com/gb/products/2862149
Inline terminal - IB IL AI 2-HART-PAC - 2862149
Connection diagram
Connection of active and passive sensors (slaves) in 2-conductor technology with shield connection
02/27/2020 Page 4 / 10
https://www.phoenixcontact.com/gb/products/2862149
Inline terminal - IB IL AI 2-HART-PAC - 2862149
Connection diagram
Connection of sensors (slaves) in a multidrop network
02/27/2020 Page 5 / 10
https://www.phoenixcontact.com/gb/products/2862149
Inline terminal - IB IL AI 2-HART-PAC - 2862149
Dimensional drawing
02/27/2020 Page 6 / 10
https://www.phoenixcontact.com/gb/products/2862149
Inline terminal - IB IL AI 2-HART-PAC - 2862149
Block diagram
Classifications
eCl@ss
eCl@ss 4.0
27250300
02/27/2020 Page 7 / 10
https://www.phoenixcontact.com/gb/products/2862149
Inline terminal - IB IL AI 2-HART-PAC - 2862149
Classifications
eCl@ss
eCl@ss 4.1
27250300
eCl@ss 5.0
27250300
eCl@ss 5.1
27242600
eCl@ss 6.0
27242600
eCl@ss 7.0
27242601
eCl@ss 8.0
27242601
eCl@ss 9.0
27242601
ETIM
ETIM 2.0
EC001431
ETIM 3.0
EC001596
ETIM 4.0
EC001596
ETIM 5.0
EC001596
ETIM 6.0
EC001596
ETIM 7.0
EC001596
UNSPSC
UNSPSC 6.01
43172015
UNSPSC 7.0901
43201404
UNSPSC 11
43172015
UNSPSC 12.01
43201404
UNSPSC 13.2
32151602
UNSPSC 18.0
32151602
UNSPSC 19.0
32151602
UNSPSC 20.0
32151602
UNSPSC 21.0
32151602
Approvals
Approvals
Approvals
UL Recognized / cUL Recognized / cULus Recognized
Ex Approvals
UL Listed / cUL Listed / ATEX / UL Listed / cUL Listed
Approval details
02/27/2020 Page 8 / 10
https://www.phoenixcontact.com/gb/products/2862149
Inline terminal - IB IL AI 2-HART-PAC - 2862149
Approvals
UL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 140324
cUL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 140324
cULus Recognized
Accessories
Accessories
Device parameterization
Software - AX+ BASIC - 2985068
Software CD for FDT container for integrating device DTMs (free download)
Labeling panel
Labeling field - IB IL FIELD 2 - 2727501
Labeling field, width: 12.2 mm
Plug
Inline shield connector - IB IL SCN 6-SHIELD-TWIN - 2740245
Inline shield connector
02/27/2020 Page 9 / 10
https://www.phoenixcontact.com/gb/products/2862149
Inline terminal - IB IL AI 2-HART-PAC - 2862149
Accessories
Inline shield connector - IB IL SCN-6 SHIELD - 2726353
Inline shield connector
Programming
Software - AX DTM LIB - 2988065
DTM library
Terminal marking
Insert strip - ESL 62X10 - 0809492
Insert strip, Sheet, white, unlabeled, can be labeled with: Office printing systems: Laser printer, mounting type: insert,
lettering field size: 62 x 10 mm, Number of individual labels: 72
Phoenix Contact 2020 © - all rights reserved
http://www.phoenixcontact.com
02/27/2020 Page 10 / 10
IB IL AI 2-HART-PAC 价格&库存